본문바로가기

Product

  • Product
  • Energy Meter

IMD

IMD (Insulation Monitoring Device) is used to detect insulation faults
in electrical systems to ensure safety and prevent damage.

IMD

Features

제품특징
제품특징 이미지

Application

제품 적용범위
  • Energy Charging Management System

    적용범위 아이콘
  • Base Station Energy Monitoring

    적용범위 아이콘
  • Energy Efficiency Management System

    적용범위 아이콘
  • IoT Cloud Platform

    적용범위 아이콘
  • Power Management System

    적용범위 아이콘
  • Hall Sensor

    적용범위 아이콘
  • Local Prepaid Solution

    적용범위 아이콘
  • Medical Institution Power Supply System

    적용범위 아이콘
  • Solar Power System

    적용범위 아이콘

Specification

라인업 & 상세스펙
Energy Meter
Technical Parameter Technical Parameter
Auxiliary power DC 9~36V
Maximum power consumption ≤6W
Voltage monitor Voltage range AIM-D100-TH : DC 100~1000V ;
AIM-D100-TL: DC 10~100V
Accuracy 0.5
Overvoltage threshold ≥110% Rated Voltage
Undervoltage threshold ≤90% Rated Voltage
Insulation monitoring Insulation resistance range 1k Ω ~ 10M Ω
Warning and alarm range 10k Ω~10M Ω
Accuracy 1~10k Ω: ±1k: 10k~500k: ≤3%
System leakage capacitance ≤5 μF
Monitoring method Cycle trigger : 5~500s delay can be set;
Communication trigger : read on demand
Insulation monitoring speed 500ms/cycle; 1000ms/cycle
Internal DC impedance <1M Ω
Alarm method LCD, LED indicator, relay output
Alarm output 3 relay outputs, N/O or N/C can be set
Contact capacity 5A 250V AC;
5A 30V DC
Fault Record 20 fault record
Communication RS485 interface, Modbus-RTU
Installation protocol
Protection level DIN-rail installation
Environment Operating temperature IP30
Storage temperature -40~+75℃
Relative humidity -40~+125℃
Altitude <95%, without condensation<2000m